STUMPY
POINT INORGANIC CHEMICAL ANALYSIS
June 12, 2006
| Name
|
Required Reporting
Limit (RRL) |
NOT Detected
Above RRL |
Quantified
Results |
Allowable
Limits |
| Arsenic, mg/l |
0.005 |
X |
|
0.010 |
| Barium, mg/l |
0.400 |
X |
|
2.000 |
| Cadmium, mg/l |
0.001 |
X |
|
0.005 |
| Chromium, mg/l |
0.020 |
X |
|
0.100 |
| Cyanide, mg/l |
0.040 |
X |
|
0.200 |
| Fluoride, mg/l |
0.100 |
|
0.890 |
4.000 |
| Iron, mg/l |
0.060 |
X |
|
0.300 |
| Manganese, mg/l |
0.010 |
X |
|
0.050 |
| Mercury, mg/l |
0.0004 |
X |
|
0.002 |
| Nickel, mg/l |
0.100 |
X |
|
N/A |
| Selenium, mg/l |
0.010 |
X |
|
0.050 |
| Sodium, mg/l |
1.000 |
|
22.400 |
N/A |
| Sulfate, mg/l |
5.000 |
X |
|
250.0 |
| Antimony, mg/l |
0.003 |
X |
|
0.006 |
| Beryllium, mg/l |
0.002 |
X |
|
0.004 |
| Thallium, mg/l |
0.001 |
X |
|
0.002 |
| pH, units |
|
|
7.90 units |
6.50-8.50 |
Page updated on August 29, 2006
Next test scheduled for 2009 |